Electrical cables are the major components of combustibles used in nuclear power plants. Therefore, fire retardant performance for electrical cables used widely in nuclear power plants had been verified according to IEEE 383 standard, which describes the requirements for the flame test for cables; however, IEEE 383 standard provides only the lowest ambient temperature (5$^\circ C$) surrounding the facilities for the flame test. To analyze the effect of the ambient temperature on fire retardant performance of cables, flame tests with two kinds of Non-Class 1E cables were conducted under the condition with the seasonal ambient temperatures surrounding the facilities. As the result of flame tests, it is found the burning length of cables does not increase in proportionally to the ambient temperature rising; but the burning length of cables decreases significantly in the winter season with the lowest ambient temperature.
원자력발전소에서 가장 큰 비중을 차지하는 가연물은 각 방화지역에 설치되어있는 케이블이라 할 수 있다. 그렇기에 원자력발전소에서 사용되는 케이블은 IEEE 383 기술기준에 따라 수행된 화염시험을 통과하여 난연성능이 검증되어야 한다. 그러나 동일 제작사에서 제작된 동일 재질의 케이블을 대상으로 케이블 화염시험을 여러차례 수행 시 케이블의 탄화길이가 현저하게 달라지는 현상이 종종 발견되었다. 본 논문에서는 이러한 현상이 화염시험 설비 주변의 최저 온도조건(5$^\circ C$)만 명시하고 있는 IEEE 383 기술기준에서 비롯된다고 생각하고, 화염시험 설비 주변의 온도변화가 케이블의 탄화길이에 영향을 줄 수 있다고 가정하였다. 이에 따라 원자력발전소에서 사용되는 두 종류의 비안전등급 케이블을 대상으로 주변 온도조건(계절조건)에 따라 화염시험을 수행하여 케이블 탄화길이의 변화를 파악하였다. 시험결과, 주변 온도의 증가에 따라 케이블 탄화길이가 비례하여 증가하지는 않았지만, 가장 낮은 주변 온도조건인 겨울 조건에서 가장 짧은 케이블의 탄화길이가 관측되고, 중간 주변 온도조건인 가을 조건에서 가장 긴 케이블의 탄화길이가 관측됨을 확인하였다.